analogue module CPX-4AE-U-I Dimensions W x L x H=(* (incl. interlinking block and connection technology), * 50 mm x 107 mm x 50 mm), No. of inputs=4, Diagnosis=(* – Wire break per channel, * – Limit value violation per channel, * – Parameterisation error, * – Overflow/underflow, * – Inlet overload, * -Short circuit in the sensor supply), Parameters configuring=(* – Data format, * Forces per channel, * – Limit monitoring/channel, * – Measured value smoothing, * – Sensor supply active, * – Signal range per channel, * – Behaviour after short circuit, * – Behaviour after inlet overload, * Monitoring of wire break/channel), LED displays=(* – 1 Group diagnosis, * – 4 Channel diagnosis)
| Dimensions W x L x HÂ | (incl. interlinking block and connection technology)50 mm x 107 mm x 50 mm |
|---|---|
| No. of inputs | 4 |
| Diagnosis | ‘- Wire break per channel- Limit value violation per channel- Parameterisation error- Overflow/underflow- Inlet overload- Short circuit of sensor supply |
| Parameters configuring | ‘- Data formatForces per channel- Limit monitoring/channel- Measured value smoothing- Sensor supply active- Signal range per channel- Behaviour after short circuit- Behaviour after inlet overloadMonitoring of wire break/channel |
| LED displays | ‘- 1 Group diagnosis- 4 Channel diagnosis |
| Internal cycle time | 500 µs |
| Repetition accuracy | 0.1% at 25º C |
| Protection (short circuit)Â | Internal electronic fuse |
| Operating voltage range DCÂ | 18 … 30 V |
| Intrinsic current consumption at operating voltage | Typically 50 mA |
| Operating error limit related to the ambient temperature range | ‘+/- 0,3 % |
| Basic error limit at 25°C | ‘+/- 0,2 % |
| Nominal DC operating voltage, load voltage | 24V +/- 2% |




Reviews
There are no reviews yet