analogue module CPX-4AE-TC Dimensions W x L x H=(* (incl. interlinking block and connection technology), * 50 mm x 107 mm x 50 mm), No. of inputs=4, Diagnosis=(* – Wire break per channel, * – Limit value violation per channel, * – Parameterisation error), Parameters configuring=(* – Limit monitoring/channel, * – Cold junction compensation, * – Unit of measurement, * – Measured value smoothing, * – Sensor type per channel, * Monitoring of wire break/channel), LED displays=(* – 1 Group diagnosis, * – 4 Channel diagnosis)
| Dimensions W x L x HÂ | (incl. interlinking block and connection technology)50 mm x 107 mm x 50 mm |
|---|---|
| No. of inputs | 4 |
| Diagnosis | ‘- Wire break per channel- Limit value violation per channel- Parameterisation error |
| Parameters configuring | ‘- Limit monitoring/channel- Cold junction compensation- Unit of measurement- Measured value smoothing- Sensor type per channelMonitoring of wire break/channel |
| LED displays | ‘- 1 Group diagnosis- 4 Channel diagnosis |
| Internal cycle time | 250 ms |
| Repetition accuracy | 0.05% at 25º C |
| Protection (short circuit)Â | Internal electronic fuse protection per channel |
| Operating voltage range DCÂ | 18 … 30 V |
| Intrinsic current consumption at operating voltage | 30 mA |
| Operating error limit related to the ambient temperature range | ‘+/- 0,6 % |
| Basic error limit at 25°C | ‘+/- 0,4 % |
| Max. line resistance | 10 ohm/conductor |