CPX-E-4AO-U-I

$546.44

SKU: 4080494 Category: Tag: Brand:
Dimensions W x L x H18.9 mm x 76.6 mm x 124.3 mm
Power supply, type of connection2x terminal strip
Vibration resistanceTransport application test with severity level 1 as per FN 942017-4 and EN 60068-2-6
Electrical connection output, connection technologySpring-loaded terminal
Permissible voltage fluctuations load± 25 %
Note on ambient temperature-5 – 60 °C for vertical installation
Intrinsic current consumption at nominal operating voltage for electronics/sensorsTypically 60 mA
Intrinsic current consumption at nominal operating voltage loadTypically 15 mA
Diagnostics via busNominal range was exceededParameterization errorLoad supply undervoltageGeneral errorActuator supply short circuit/overloadAnalog output short circuit/overloadNominal range not reached
Power supply, connection pattern995847
Electrical connection output, functionAnalog output
Electrical connection output, connection type4x terminal strip
Power supply, information on conductor diameter0.2 – 2.5 mm² for flexible conductors without cable end sleeves
Permissible voltage fluctuations for electronics/sensors± 25 %
Power supply, connection technologySpring-loaded terminal
Electrical connection for output, information on conductor cross section0.2 – 2.5 mm² for flexible conductors without cable end sleeves
Shock resistanceShock test with severity level 1 as per FN 942017-5 and EN 60068-2-27
Signal range4 – 20 mA0 – 10 V-10 – 10 V-20 – 20 mA0 – 20 mA-5 – 5 V
Module parametersParameterization error diagnosticsDeactivate actuator supplyActuator supply short circuit diagnosticsResponse to actuator supply short circuit/overloadAnalog output data formatLoad supply undervoltage diagnosticsResponse to analog output short circuit/overload
Channel parametersForcing channel xEnable overload/short circuit diagnosticsSignal range per channelEnable parameterization error diagnosticsEnable wire break/idling diagnostics
Diagnostics via LEDFaults per channelFaults per module
Electrical connection for output 2, connection pattern995842
Electrical connection for output 2, Information on conductor cross section0.2 – 2.5 mm² for flexible conductors without cable end sleeves
Electrical connection output 2, connection typeTerminal strip
Electrical connection output 2, connection technologySpring-loaded terminal
Nominal operating voltage DC for electronics/sensors24 V
Electrical output connection, number of pins/wires4
Power supply, number of pins/wires4
Nominal operating voltage DC load24 V
Electrical output connection 2, number of pins/wires4
Power supply, conductor diameter0.2 mm² … 1.5 mm²
Electrical connection for output, conductor cross section0.2 mm² … 1.5 mm²
Electrical connection for output 2, conductor cross section0.2 mm² … 1.5 mm²
Width dimension18.9 mm
Type codeCPX-E
No. of outputs4
Measured variableVoltageCurrent
Repetition accuracy±0.05 % at 25 °C
Fuse protection (short circuit)Internal electronic fuse per module
Operating error limit related to the ambient temperature range+/- 0.3 %
Basic error limit at 25°C+/- 0.1 %
Max. residual current of outputs per module0.0833333333333333
Power failure buffering10 ms
Electrical isolation between channel and internal busyes
Electrical isolation between channelsno
CE marking (see declaration of conformity)As per EU EMC directive
Corrosion resistance class (CRC)0 – No corrosion stress
Storage temperature-20 °C … 70 °C
Relative air humidity95 %Non-condensing
Protection against direct and indirect contactPELV
Degree of protectionIP20
Ambient temperature-5 °C … 50 °C
CertificationRCM compliance mark
Product weight96 g
Max. address capacity outputs8 byte
Data format15 bit + signLinear scaling
Max. cable lengthShielded30 m
Type of mountingWith H-rail
Note on materialsContains paint-wetting impairment substancesRoHS-compliant
Housing materialPA