Dimensions W x L x H | 18.9 mm x 76.6 mm x 124.3 mm |
---|---|
Power supply, type of connection | Terminal strip |
Vibration resistance | Transport application test with severity level 1 as per FN 942017-4 and EN 60068-2-6 |
Permissible voltage fluctuations load | ± 25 % |
Note on ambient temperature | -5 – 50 °C for horizontal installation |
Intrinsic current consumption at nominal operating voltage for electronics/sensors | Typically 50 mA |
Intrinsic current consumption at nominal operating voltage load | Typically 15 mA |
Diagnostics via bus | Wire breakUnderflow/overflowShort circuitGeneral errorParameter errorModule errorDevice missing/failedUndervoltage |
Power supply, connection pattern | 995847 |
Power supply, information on conductor diameter | 0.2 – 2.5 mm² for flexible conductors without cable end sleeves |
Permissible voltage fluctuations for electronics/sensors | ± 25 % |
Power supply, connection technology | Spring-loaded terminal |
Shock resistance | Shock test with severity level 1 as per FN 942017-5 and EN 60068-2-27 |
Module parameters | Actuator supply short circuit diagnosticsResponse to short circuit/overloadDeactivate sensor supply |
Channel parameters | Forcing channel xCycle timeChannel statusDeactivate actuator supplyChannel modeDevice fault code |
Diagnostics via LED | Faults per moduleStatus per channel |
Electrical connection, IO-Link®, connection technology | Spring-loaded terminal |
Electric IO-Link® connection, connection pattern | 995843 |
Electrical IO-Link® connection, connection type | 4x terminal strip |
IO-Link®, communication | C/Q LED green |
IO-Link® electrical connection, information on conductor cross section | 0.2 – 2.5 mm² for flexible conductors without cable end sleeves |
Nominal operating voltage DC for electronics/sensors | 24 V |
Power supply, number of pins/wires | 4 |
Electrical IO-Link® connection, number of pins/wires | 6 |
Power supply, conductor diameter | 0.2 mm² … 1.5 mm² |
IO-Link® electrical connection, conductor cross section | 0.2 mm² … 1.5 mm² |
Width dimension | 18.9 mm |
Type code | CPX-E |
Fuse protection (short circuit) | Internal electronic fuse, load per channelInternal electronic fuse, sensor per module |
Electrical isolation between channel and internal bus | no |
Electrical isolation between channels | no |
CE marking (see declaration of conformity) | As per EU EMC directive |
Corrosion resistance class (CRC) | 0 – No corrosion stress |
Storage temperature | -20 °C … 70 °C |
Relative air humidity | 95 %Non-condensing |
Protection against direct and indirect contact | PELV |
Degree of protection | IP20 |
Ambient temperature | -5 °C … 50 °C |
Certification | RCM compliance mark |
Product weight | 96 g |
Protocol | IO-Link® |
IO-Link®, protocol version | Master V 1.1 |
IO-Link®, communication mode | SIO, COM1 (4.8 kBd), COM2 (38.4 kBd), COM3 (230.4 kBd)Configurable via software |
IO-Link®, port class | B |
IO-Link®, number of ports | 4 |
IO-Link®, process data width OUT | 8–32 bytes parameterizable |
IO-Link®, process data width IN | 8–32 bytes parameterizable |
IO-Link®, minimum cycle time | Depends on minimally supported cycle time of connected IO-Link® device |
Type of mounting | With H-rail |
Note on materials | Contains paint-wetting impairment substancesRoHS-compliant |
Housing material | PA |
Only logged in customers who have purchased this product may leave a review.
Reviews