Dimensions W x L x H | 30 mm x 170 mm x 35 mm |
---|---|
KC characters | KC EMC |
Diagnose per internal communication | Wire breakModule errorShort circuit/overload in sensor supplyParameter errorParameterization errorOverload at analog inputsUpper limit value violatedUnderflow/overflowLower limit value not complied with |
Max. power supply | 2 x 4 A (external fuse required) |
Note on degree of protection | Unused connections sealed |
Fuse protection inputs (short circuit) | Internal electronic fuse per module |
Communication interface, connection technology | M8x1, D-coded as per EN 61076-2-114 |
Permissible voltage fluctuations for electronics/sensors | ± 25 % |
Power supply, connection technology | M8x1, A-coded as per EN 61076-2-104 |
Power supply, function | Incoming electronics/sensors and load |
Voltage forwarding, connection technology | M8x1, A-coded as per EN 61076-2-104 |
Relative air humidity | 5 – 95 %Non-condensing |
Communication interface, connection type | 2x socket |
Intrinsic current consumption at nominal operating voltage for electronics/sensors | Typically 38 mA |
Power supply, type of connection | Plug |
Voltage forwarding, connection type | Socket |
Communication interface, function | System communication XF10 IN / XF20 OUT |
Max. cable length | 30 m inputs50 m system communication |
Electrical connection input, function | Analog input |
Communication interface, protocol | AP-COM |
Digital inputs, electrical isolation of input – internal communication | yes |
Diagnostics via LED | Diagnostics per moduleStatus per channel |
Electrical isolation of inputs between channels | no |
Electrical connection input, connection type | 4x socket |
Communication interface, shielding | yes |
Voltage forwarding, function | Outgoing electronics/sensors and load |
Electrical input connection, connection technology | M12x1 A-coded as per EN 61076-2-101 |
Electrical connection, input, number of pins/wires | 5 |
Voltage forwarding, number of pins/wires | 4 |
Nominal operating voltage DC for electronics/sensors | 24 V |
Power supply, number of pins/wires | 4 |
No. of inputs | 4 |
Communication interface, number of pins/wires | 4 |
Max. residual current of inputs per module | 1 A |
Power failure buffering | 10 ms |
Note regarding operating voltage | SELV/PELV fixed power supplies requiredNote voltage drop |
Electrical connection, input, note on connection technology | To achieve the technical specifications, the opposite side is shielded and must be designed with contact surfaces made from gold. |
Basic error limit at 25°C | ±0.1 % for voltage±0.1 % for electrical current±0.2 % for resistor±0.4 % for temperature |
Measured variable | VoltageCurrentTemperatureResistor |
Data format | 15 bit + signLinear scaling |
Repetition accuracy | ±0.025 % at 25 °C |
Signal range | -10 – 10 V-5 – 5 V0 – 10 V0 – 20 mA0 – 500 Ω1 – 5 V4 – 20 mA |
Operating error limit related to the ambient temperature range | ±0.15 % for voltage±0.15 % for electrical current±0.35 % for resistor±0.9 % for temperature |
Type code | CPX-AP-I |
Reverse polarity protection | yes |
CE marking (see declaration of conformity) | As per EU EMC directive |
Corrosion resistance class (CRC) | 1 – Low corrosion stress |
Storage temperature | -40 °C … 70 °C |
Degree of protection | IP65IP67 |
Ambient temperature | -20 °C … 50 °C |
Certification | RCM compliance mark |
Product weight | 166 g |
Type of mounting | With through-hole |
Note on materials | RoHS-compliant |
Housing material | PAPCDie-cast zinc, nickel-plated |
CPX-AP-I-4AI-U-I-RTD-M12
$546.44
GTIN: 4052568550110
Only logged in customers who have purchased this product may leave a review.
Reviews
There are no reviews yet