Dimensions W x L x H | (incl. interlinking block and connection system)50 mm x 107 mm x 70 mm |
---|---|
Vibration resistance | Transport application test with severity level 2 as per FN 942017-4 and EN 60068-2-6 |
Shock resistance | Shock test with severity level 2 as per FN 942017-5 and EN 60068-2-27 |
Signal range | 0 – 20 mA4 – 20 mA4–20 mA with HART |
Min. available sensor voltage | 20.7 V at 20 mA |
Number of selectable analog inputs/outputs | 4 |
Max. input resistance | 300 Ohm |
Max. open circuit voltage | 28.8 V |
Max. short circuit current | 22 mA |
Max. load | 750 Ohm |
Width dimension | 50 mm |
Type code | CPX |
Diagnostics | Wire break per channelLimit value violation per channelLimit value violation as per NE43 per channelShort circuit/overload per channelParameterization errorOverflow/underflow |
Parameterization | Data formatFail-safe modes per channelForcing per channelLimit value monitoring per channelIdle mode per channelMeasured value smoothingSignal range per channelOverflow/underflow monitoringMonitoring according to NE43 inputsWire break monitoring per channelWire break per channelLimit value violation per channelShort circuit/overload per channelParameterization errorOverflow/underflowLimit value violation as per NE43 per channelNumber of HART repetitionsHysteresis for critical limitsHART variablesResponse to short circuit/overload |
Reverse polarity protection | for all electrical connections |
Control elements | DIL switch |
LED indicators | 1 group diagnostics4 channel diagnostics4 channel status |
Repetition accuracy | 0.05 % at 25 °C |
Fuse protection (short circuit) | Internal electronic fuse per channel |
DC operating voltage range | 18 V … 30 V |
Intrinsic current consumption at nominal operating voltage | Typ. 170 mA |
Operating error limit related to the ambient temperature range | ±0.3 % |
Basic error limit at 25°C | ±0.1 % |
Nominal operating voltage DC | 24 V |
Power failure buffering | 10 ms |
Electrical isolation between channel and internal bus | yes |
Electrical isolation between channels | no |
CE marking (see declaration of conformity) | As per EU EMC directive |
Corrosion resistance class (CRC) | 1 – Low corrosion stress(when installed) |
Storage temperature | -20 °C … 70 °C |
Relative air humidity | 95 %Non-condensing |
Degree of protection | Depends on manifold block |
Ambient temperature | -5 °C … 50 °C |
Product weight | 77.4 g |
Data format | 15 bit + signScalable to 15 bits |
Protocol | HART |
Max. cable length | 500 m |
Sensor type | 0 – 20 mA4 – 20 mA4–20 mA with HART |
Type of mounting | On interlinking block |
Note on materials | RoHS-compliant |
Housing material | PA-reinforcedPC |
Only logged in customers who have purchased this product may leave a review.
Reviews
There are no reviews yet